kWPVdc = (CFA x A)/1000
WHERE:
- kWPVdc = Size of the PV system in kW
- CFA = Conditioned floor area in square feet
- A = PV capacity factor specified in Table 140.10-A for the building type
Where the building includes more than one of the space types listed in Table 140.10-A, the total PV system capacity for the building shall be determined by applying Equation 140.10-A to each of the listed space types and summing the capacities determined for each.
kWhbatt = kWPVdc x B / D0.5
WHERE:
kWhbatt = Rated Useable Energy Capacity of the battery storage system in kWh
kWPVdc = PV system capacity required by section 140.10(a) in kWdc
B = Battery energy capacity factor specified in Table 140.10-B for the building type
D = Rated single charge-discharge cycle AC to AC (round-trip) efficiency of the battery storage system
kWbatt = kWPVdc x C
WHERE:
kWbatt = Power capacity of the battery storage system in kWdc
kWPVdc = PV system capacity required by section 140.10(a) in kWdc
C = Battery power capacity factor specified in Table 140.10-B for the building type
EXCEPTION 1 to Section 140.10(b). No battery storage system is required if the installed PV system size is less than 15 percent of the size determined by Equation 140.10-A.
EXCEPTION 2 to Section 140.10(b). No battery storage system is required in buildings with battery storage system requirements with less than 10 kWh rated capacity.
EXCEPTION 3 to Section 140.10(b). For multi-tenant buildings, the energy capacity and power capacity of the battery storage system shall be based on the tenant spaces with more than 5,000 square feet of conditioned floor area. For single-tenant buildings with less than 5,000 square feet of conditioned floor area, no battery storage system is required.
EXCEPTION 4 to Section 140.10(b). In Climate Zone 1, no battery storage system is required for offices, schools, and warehouses.
Factor A – Minimum PV Capacity (W/ft² of conditioned floor area) | |||
Climate Zone | 1, 3, 5, 16 | 2, 4, 6-14 | 15 |
Grocery | 2.62 | 2.91 | 3.53 |
High-Rise Multifamily | 1.82 | 2.21 | 2.77 |
Office, Financial Institutions, Unleased Tenant Space | 2.59 | 3.13 | 3.80 |
Retail | 2.62 | 2.91 | 3.53 |
School | 1.27 | 1.63 | 2.46 |
Warehouse | 0.39 | 0.44 | 0.58 |
Auditorium, Convention Center, Hotel/Motel, Library, Medical Office Building/Clinic, Restaurant, Theater | 0.39 | 0.44 | 0.58 |
Factor B – Energy Capacity | Factor C – Power Capacity | |
Storage-to-PV Ratio | Wh/W | W/W |
Grocery | 1.03 | 0.26 |
High-Rise Multifamily | 1.03 | 0.26 |
Office, Financial Institutions, Unleased Tenant Space | 1.68 | 0.42 |
Retail | 1.03 | 0.26 |
School | 1.87 | 0.46 |
Warehouse | 0.93 | 0.23 |
Auditorium, Convention Center, Hotel/Motel, Library, Medical Office Building/Clinic, Restaurant, Theater | 0.93 | 0.23 |
NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.